Engineering manual - SAB 193-233-283 S A-frame (including ATEX)
008831 en 2020.10
155/168
Transport instructions
manufacturers have lower limits for standstill vibrations. Cover the unit to protect it from dust
and dirt. The unit must not be stored with other objects giving off acidic vapours or the like, as this
can have a corrosive effect on the unit. It is moreover required that the store room is dry (non-
condensing) and frost-free.
When stored, the unit must be inspected at regular intervals. Every three months, the compres-
sor must be rotated 8-10 turns to prevent the oil in the bearings from drying out. Be aware that
some motor manufacturers may require more frequent rotation of shafts. As far as the motor is
concerned, check the lubricating nipples and lubricate them if necessary.