Technical data
6.4 Minimum compressor flow at 3550 rpm
The minimum flow capacity for each compressor varies depending on its geometry and its operat-
ing conditions. Typical minimum flow for each of our compressor models is listed below. Table 22
represents minimum suction flow with the slide valve fully unloaded.
Unit
Minimum flow*
CFM
m
3
/h
SAB 193 S
71
121
SAB 193 L 95 161
SAB 233 S 125 212
SAB 233 L 157 267
SAB 233 E 365 621
SAB 283 S 224 380
SAB 283 L 282 479
SAB 283 E 650 1104
SAB 283 X 478 812
Table 22: Minimum suction flow
* at 3550 rpm