EasyManuals Logo

Johnson Controls IFI-WS User Manual

Johnson Controls IFI-WS
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
Product Overview Additional Software
10 IFI-WS Installation and Operation Manual – P/N LS10050-000JC-E:A 12/11/2014
1.2.2 System Limits
The IFI-WS is designed to operate within the limits listed below:
1.3 Additional Software
1.3.1 Anti-virus Software
Recommended and tested against McAfee Enterprise.
1.3.2 Windows Automatic Updates
Must be set to “Check for updates but let me choose whether to download and install them”.
1.4 Environmental Requirements
This product meets the following requirements for operation:
Temperature - 0°C to 49°C (32°F - 120°F)
Relative Humidity - 93 ±2% non-condensing at 32 ±2°C (90 ±3°F)
However, it is recommended that this product be installed in an environment with a normal room
temperature of 15-27º C (60-80º F).
Table 1.1 System Limits
Limit Feature Maximum Allowed
Physical Network Limit Gateways 200 total
Logical Network & Screen Screens 1000
Devices 100,000
Macros 100
Macro Button 100
NavIcons 1000
Monitoring Profiles 100
Node Control Profiles 100
Workstation Output Formats 25 per Workstation
Email Recipients 10 per Workstation
Email Recipients (MNS) 5 per Event
Pager Recipients 10 per Workstation
Pager Recipients (MNS) 5 per Event
Maximum Workstations per
system
50 Workstations
User Manager Users 500

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls IFI-WS and is the answer not in the manual?

Johnson Controls IFI-WS Specifications

General IconGeneral
BrandJohnson Controls
ModelIFI-WS
CategorySecurity System
LanguageEnglish

Related product manuals