14 IFI-WS Installation and Operation Manual – P/N LS10050-000JC-E:A 12/11/2014
1.7.2 Agency Restrictions and Limitations
•If the IFI-WS or the transmitter is sharing on-premises communications equipment, the shared
equipment shall be "listed for the purpose"; otherwise the transmitter must be installed ahead of the
unlisted equipment. “Listed for the purpose” has been formally interpreted by NFPA (Formal
Interpretation 72-99-1) for equipment on packet switched networks as being listed to the
requirements applicable to general purpose communications network equipment.
The IFI-WS is UL listed only for monitoring when using an Ethernet connection for communications
with a life safety network. The Ethernet connection can be part of, or connected to, a shared
bandwidth network that operates over topologies such as an intranet, the Internet, or a frame relay.
•The IFI-WS uses active communication for monitoring of devices. In Canada, infrastructure which
involves LAN/WAN configurations may be used for monitoring of fire networks provided that a
dedicated T-1 line is used and routers are battery backed with a power source capable of providing
backup power for a period of 24 hours.
The UL listing for the IFI-WS includes the ability for the workstation to send notifications to
alphanumeric pagers. These notifications are intended to be transmitted to only a limited number of
staff (refer to Table 1.1 for details) for maintenance purposes and system status reasons. This feature
is approved by UL as supplementary.
The UL listing for the IFI-WS includes the ability for the workstation to send emails. These emails
are intended to be transmitted to a limited number of staff (refer to Table 1.1 for details) for
maintenance purposes and system status reasons. This feature is approved by UL as supplementary.
The IFI-WS must be continuously monitored by trained, competent personnel.
•When operating as a Proprietary Receiving Unit, the IFI-WS is UL listed only for monitoring of fire
and mass notification devices.
•When operating as a Protected Premises Control Unit, the IFI-WS is UL listed for monitoring and
control of fire and mass notification devices.
•In Canada, when operating as a Proprietary Receiving Unit, the IFI-WS is ULC listed only for
monitoring of fire devices and must be configured in “Canada – Receiving Unit” mode.
•In Canada, when operating as a Protected Premises Control Unit, the IFI-WS is ULC listed for
monitoring and control of fire devices and must be configured in “Canada - Protected Premises
Control Unit” mode or “Canada – Protected Premises Control Unit + DCC’(Display and Control
Centre) mode.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls IFI-WS and is the answer not in the manual?

Johnson Controls IFI-WS Specifications

General IconGeneral
BrandJohnson Controls
ModelIFI-WS
CategorySecurity System
LanguageEnglish

Related product manuals