Power Requirements
2–8 iSTAR Ultra Installation and Configuration Guide
Maximum Power
The ISTAR Ultra system power ratings are listed in Table 2-6 through Table 2-8.
Table 2-6: iSTAR Ultra GCM Rack System Ratings
Voltage
(Vdc)
Current
(A)
Local External
Circuit Breaker
Rating (A)
System Description
System Power Ratings:
12 4.49 - (1) GCM with (2) RS-485 Loads
Table 2-7: iSTAR Ultra ACM Rack Ratings
Voltage
(Vdc)
Current
(A)
Local External
Circuit Breaker
Rating (A)
System Description
System Power Ratings:
12 5 - (1) ACM with (3) Wiegand/RS485/Aux load
12 8 10 (1) ACM with (5) Wiegand/RS485/Aux load
12 9.5 12 (1) ACM with (6) Wiegand/RS485/Aux load
12 11 15 (1) ACM with (7) Wiegand/RS485/Aux load
12 12.5 29 (1) ACM with (8) Wiegand/RS485/Aux load
Lock 1 and 2 Power Ratings:
0 - 30 4.5 - (6) Locks
0 - 30 6 7.5 (8) Locks
0 - 30 7.5 10 (10) Locks
0 - 30 9 12 (12) Locks
0 - 30 12 15 (16) Locks
Table 2-8: iSTAR Ultra Wall Mount Ratings
Voltage
(Vdc)
Current
(A)
Local External
Circuit Breaker
Rating (A)
System Description
System Power Ratings (when sourcing both GCM and ACMs):
12 3.99 - (1) GCM with (1) RS-485 Loads & (2) ACM with no loads
12 4.99 - (1) GCM with (2) RS-485 Loads & (1) ACM with no loads
12 7.99 10 (1) GCM with (2) RS-485 Loads & (1) ACM with
(2) Wiegand/RS485/Aux load
12 9.49 12 (1) GCM with (2) RS-485 Loads & (1) ACM with
(3) Wiegand/RS485/Aux load