EasyManua.ls Logo

Johnson Controls tyco iSTAR Ultra - Relay Wiring

Johnson Controls tyco iSTAR Ultra
118 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Access Control Module
5–14 iSTAR Ultra Installation and Configuration Guide
Form C
Jumper for each relay to select Wet/Dry and Wet power source
It is convenient to configure a Door with all the components together in one of these sections,
but it is not a requirement. However, all door components must come from the same
controller.
Use the C•CURE Administration Workstation to configure the output as Normally Energized
for the Fail Safe case.
Dry Relay Wiring
Figure 5-12 on page 5-14 shows DRY relay wiring. Use NO or NC as appropriate. Notice that
jumper is in the Dry position.
Figure 5-12: Dry Relay Wiring
Wet Relay Wiring
Figure 5-13 on page 5-15 shows Wet wiring for a normal NO Latch. The iSTAR Ultra will
supply 0 to 30 Vdc, depending on the input supply. Current is limited to 0.75 A. Notice that the
GND is used for common, not the C pin. Notice that the jumper is in the Wet position.

Table of Contents

Related product manuals