Inputs
5–20 iSTAR Ultra Installation and Configuration Guide
200/10K Double NO
(Infographics)
Parallel and Serial Resistors
Normal = 10K
Alert = 196
1K Double NC (Casi-Rusco) Serial and Parallel Resistors
Normal = 1K
Alert = 2K
1K Double NO (Casi-Rusco) Parallel and Serial Resistors
Normal = 2K
Alert = 1K
5K Double NC (Simplex) Serial and Parallel Resistors
Normal = 5K
Alert = 10K
5K Double NO (Simplex) Parallel and Serial Resistors
Normal = 10K
Alert = 5K
10K Double NC (Andover)
Normal = 5K
Alert = 10K
10K Double NO (Andover)
Normal = 10K
Alert = 5K
4.02K/8.04K Triple NC
(Atlantek)
Normal = 4.02K, Tamper = 10.06K
Alert = 8.04K, Tamper + Alarm = 14.08K
Table 5-8: Supervision Modes, continued
Mode Comment