APPENDIX B - PROGRAMMABLE SETPOINT VALUES
HARMONIC FILTER DETAILS SCREEN (HARMONIC FILTER SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Motor Current Limit Operator 30 % 100 % 100 %
Pulldown Demand Limit Operator 30 % 100 % 100 %
Pulldown Demand Time Operator 0 Min 255 Min 0 Min
MOTOR TEMPERATURE SCREEN (MOTOR SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Winding Sensor Mode Service
None, Analog, Digital, Analog and
Digital
None
Winding Cutout Service 150 °F 300 °F 265 °F
Bearing Sensor Mode Service
None, Analog, Digital, Analog and
Digital
None
Bearing Cutout Service 100 °F 180 °F 180 °F
Motor Cooling Pump Service Disabled Enabled Disabled
Motor Cooling Pump Mode Service Automatic Manual Automatic
Phase A (Active Sensor) Service None, A1, A2, A1 and A2 None
Phase B (Active Sensor) Service None, B1, B2, B1 and B2 None
Phase C (Active Sensor) Service None, C1, C2, C1 and C2 None
Bearing (Active Sensor) Service
None, Sensor 1, Sensor 2,
Sensor 1 and 2
None
SETPOINTS SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Leaving Chilled Liquid Temperature - Setpoint Operator
38.0 °F - Water
36.0 °F - Sm Frz
10.0 °F - Brine
70.0 °F 45.0 °F
Local Leaving Chilled Liquid Temperature - Range Operator 10.0 °F 20.0 °F 20.0 °F
LCHLT Cycling Offset - Shutdown Operator 1.0°F 64.0 °F
4.0 °F or high-
est allowed
value, which-
ever is lower.
LCHLT Cycling Offset - Restart Operator 0.0 °F 70.0 °F 0.0 °F
Remote Analog Input Range Operator 0 - 10 VDC 2 - 10 VDC 0 - 10 VDC
Motor Current Limit Operator 30 % 100 % 100 %
Pulldown Demand Limit Operator 30 % 100 % 100 %
Pulldown Demand Time Operator 0 Min 255 Min 0 Min
TABLE 13 - PROGRAMMABLE SETPOINT VALUES (CONT’D)