APPENDIX B - PROGRAMMABLE SETPOINT VALUES
HARMONIC FILTER DETAILS SCREEN (HARMONIC FILTER SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Motor Current Limit Operator 30 % 100 % 100 %
Pulldown Demand Limit Operator 30 % 100 % 100 %
Pulldown Demand Time Operator 0 Min 255 Min 0 Min
MOTOR TEMPERATURE SCREEN (MOTOR SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Winding Sensor Mode Service
None, Analog, Digital, Analog and
Digital
None
Winding Cutout Service 150 °F 300 °F 265 °F
Bearing Sensor Mode Service
None, Analog, Digital, Analog and
Digital
None
Bearing Cutout Service 100 °F 180 °F 180 °F
Motor Cooling Pump Service Disabled Enabled Disabled
Motor Cooling Pump Mode Service Automatic Manual Automatic
Phase A (Active Sensor) Service None, A1, A2, A1 and A2 None
Phase B (Active Sensor) Service None, B1, B2, B1 and B2 None
Phase C (Active Sensor) Service None, C1, C2, C1 and C2 None
Bearing (Active Sensor) Service
None, Sensor 1, Sensor 2,
Sensor 1 and 2
None
SETPOINTS SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Leaving Chilled Liquid Temperature - Setpoint Operator
38.0 °F - Water
36.0 °F - Sm Frz
10.0 °F - Brine
70.0 °F 45.0 °F
Local Leaving Chilled Liquid Temperature - Range Operator 10.0 °F 20.0 °F 20.0 °F
LCHLT Cycling Offset - Shutdown Operator 1.0°F 64.0 °F
4.0 °F or high-
est allowed
value, which-
ever is lower.
LCHLT Cycling Offset - Restart Operator 0.0 °F 70.0 °F 0.0 °F
Remote Analog Input Range Operator 0 - 10 VDC 2 - 10 VDC 0 - 10 VDC
Motor Current Limit Operator 30 % 100 % 100 %
Pulldown Demand Limit Operator 30 % 100 % 100 %
Pulldown Demand Time Operator 0 Min 255 Min 0 Min
TABLE 13 - PROGRAMMABLE SETPOINT VALUES (CONT’D)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls YORK OPTIVIEW CONTROL CENTER and is the answer not in the manual?

Johnson Controls YORK OPTIVIEW CONTROL CENTER Specifications

General IconGeneral
BrandJohnson Controls
ModelYORK OPTIVIEW CONTROL CENTER
CategoryControl Panel
LanguageEnglish

Related product manuals