1.4 Unitidentication
C6 Material number Description
Compact
00C6BA1-(x)A(y)0 4DI/4DO
COMPACT II
00C6BD1-(x)C(y)0 4DI/4DO
(x) = eldbus module: A = no, B = PROFIBUS slave, C = CAN, D = INTERBUS slave
(y) = soft option: A = no, B = soft motion
Examples:
00C6BA1-AAB0 C6-Compact 4DI/4DO + soft motion
00C6BA1-BAB0 C6-Compact 4DI/4DO + PROFIBUS slave + soft motion
00C6BA1-CAA0 C6-Compact 4DI/4DO + CAN
00C6BA1-DAA0 C6-Compact 4DI/4DO + INTERBUS slave
00C6BD1-ACA0 C6-Compact II 4DI/4DO
00C6BD1-BCA0 C6-Compact II 4DI/4DO + PROFIBUS Slave
00C6BD1-CCB0 C6-Compact II 4DI/4DO + CAN + Softmotion
1.5 Technical data
General
Dimensions (HxBxT) 125 x 44 x 144 mm
Weight approx. 260 g
Installation method 35 mm Mounting rail
Grounding via terminal strip or plug-in contact
Protective system (EN 60529): IP20
Operation temperature -10…45 °C (14…113 °F)
Storage temperature -25…70 °C (-13…158 °F)
Climatic category (EN 60721-3-3): 3K3
Environment (IEC 664-1) Pollution degree 2
Control
Operating voltage control (US) 18…30 V DC ±0 %
Power input control 3 W max.
Digital inputs/outputs
Wiring system cage-clamp terminals
Operating voltage inputs/outputs (UM) 18…30 V DC ±0 %
Output current max. 0.7 A per channel, short-circuit proof, free-
wheeling diode integrated
Input voltage/current according to IEC 61131-2 Type 1