EasyManuals Logo

KEB combivert R6-S Applications Manual

KEB combivert R6-S
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
Seite 3.4 - 6 COMBIVERT R6-S © KEB, 2008-02
Digital in- and outputs
3.4.5 Digital noise lter (di.03)
Thedigitalnoiselterreducesthesensitivityagainstdisturbancesatthedigitalinputs.Onlyhardwareinputs
canbeltered.Eachinputhasaseparateltercounter,whichcountsupwardatactiveinputanddownwardat
inactiveinput.Theoutputofthelterissetonreachingtheltertimeandresetwhenreaching zero.
Parameter Setting range Resolution
di.03 0...127 ms 1 ms
Priorityoftheltertimes:thehighertimeisused.
3.4.6 Invert the inputs (di.04)
With parameter di.04 can be adjusted whether a signal is 1- or 0- active (inverted). The parameter is bit-coded,
i.e. the appropriate value of the input must be entered. If several inputs shall be inverted, the sum is to be for-
med(Exception:invertingofthecontrolreleaseremainswithoutfunction).
3.4.7 Input trigger (di.05)
As standard the COMBIVERT is controlled with static signals i.e., an input is set as long as a signal is active.
But in practice it may happen that a signal is only available temporary, but the input shall remain set. For this
case this or several inputs can be set to input trigger. A rising slope with a pulse duration, which is longer than
theresponsetimeofthedigitallteris sufcientforswitchingon.Switchingoffisdonewiththenextrisingslo-
pe.
Control release (ST) can be adjusted to input trigger, but this has no effect to the function, since this is a static
signal.
Picture3.4.7Exampleofasignalowdiagramforinput(di.05 = 16)
Slope-triggering
t
t
Input trigger
3.4.8 Strobe-dependent inputs (di.06, di.07, di.08)
A strobe signal is mainly used for triggering the input signals. For example, two inputs are used for parameter
set selection. The incoming signals to the control are not simultaneously, so that it would be switched into an
unwanted set for a short-time. For active strobe (scanning signal) the actual input signals of the strobe-depen-
dent inputs are stored and have been retained to the next scanning.

Table of Contents

Other manuals for KEB combivert R6-S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB combivert R6-S and is the answer not in the manual?

KEB combivert R6-S Specifications

General IconGeneral
BrandKEB
Modelcombivert R6-S
CategoryPower Supply
LanguageEnglish

Related product manuals