Error assistance
© KEB, 2008-02 COMBIVERT R6-S Page 5.1 - 5
5
Display COMBIVIS Value Meaning
E.SEt Error ! Set 39
It has been attempted to select a locked parameter set. Programmed
response “Error, restart after reset”.
E.SYn Error! Synchronization 59 Phase allocation at commutation choke not correct.
E. UP Error ! Undervoltage 2
Error:Undervoltage(DC-link circuit). Occurs, if DC-link voltage falls
belowthepermissiblevalue.Causes:
- input voltage too low or unstable
- Transformer capacity too small
- voltage losses through wrong cabling
Warning Messages
A.buS Warning ! Watchdog 93
Watchdog for communication between operator / PC or operator
/ inverter has responded. The response to this warning can be
programmed.
A. EF
Warning ! ERROR external
fault
90
This warning is triggered via an external input. The response to this
warning can be programmed.
A.nOH
no ABN.STOP Power module
temperature
88 The heat sink temperature is again below the adjusted warning level.
A.nOHI
no ABN.STOP Interior
temperature
92
The temperature in the interior of the inverter is again below the
warning threshold.
A.nOL no ABN.STOP Overload 98
Warning:nomoreoverload,OLcounterhasreached0%,warning
„overload" can be reset.
A. OH
Warning ! Power module
temperature
89
A levelcanbedened, whenitisexceededthiswarning isoutput.
Furthermore the response to this warning can be programmed.
A.OHI
Warning ! Interior
temperature
87
The temperature in the interior of the inverter lies above the permissible
level. The switch off time was started. The programmed response to
this warning message is executed.
A. OL Warning ! Overload 99
A level between 0 and 100% of the load counter can be adjusted, when
it is exceeded this warning is output. The response to this warning can
be programmed.
A.SEt Warning ! Set 102
It has been attempted to select a locked parameter set. The response
to this warning can be programmed.

Table of Contents

Other manuals for KEB combivert R6-S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB combivert R6-S and is the answer not in the manual?

KEB combivert R6-S Specifications

General IconGeneral
BrandKEB
Modelcombivert R6-S
CategoryPower Supply
LanguageEnglish

Related product manuals