Regenerative adjustments
© KEB, 2008-02 COMBIVERT R6-S Page 3.5 - 3
3
10
3.5 Regenerative adjustments
3.5.1 Operating mode
Operating mode Pn.19determines:
- if the unit is a master or a slave
- Unit is operated with commutation choke or harmoniclter
Commutation choke
Advantages Disadvantages
· cheap purchase · only for area of industry
Harmoniclter
Advantages Disadvantages
· sine-wave regeneration · high purchase cost
Pn.19: Operating mode
Value Default Note
0: Master with commutation choke X
For high power regenerative units can be parallel con-
nected.
Here,adevicemustbespeciedasmaster.Allfurtherare
adjusted as slave. Single units are alwags master.
The coupling of the regenerative units is made by termi-
nals X2A.16/18, since this is a fast digital input.
1:Masterwithharmoniclter
2: Slave with commutation choke
3:Slavewithharmoniclter
If R6 units of different size are parallel connected, it is recommended, to denethelargerunitasma-
ster.
With changing of the adjustment of Pn.19 the parameterizing of cS.00, cS.01 and cS.04 for the KEB standard
commutation choke or the KEB standard harmoniclterispreset.WhenusingKEBproductsnofurtherpa-
rameter setting is necessary. The values of cS.00, cS.01 and cS.04 are overwritten at external products with
response of Pn.19.
IftheR6isoperatedasamaster,I4(X2A.16)isautomaticallyconguredasdigitaloutput, if the R6 is operated
asaslave,X2A.16conguredasdigitalinput.
3.5.2 Setting of the choke rating data or harmonic lter
The regenerative unit calculates the voltage losses at the input with the following two parameters. The parame-
ters are preset with parameter Pn.19.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
cS.00 Choke/ rated voltage 0F00h rw - - 0 1000 1 V var
Setting in accordance with the datasheetofthechokerespectivelyharmoniclter.Thedefaultvalueis0at
thepoweradaptedharmoniclter.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
cS.01 Choke / rated current 0F01h rw - - 0 5000 1 A var
Setting in accordance with the datasheetofthechokerespectivelyharmoniclter.

Table of Contents

Other manuals for KEB combivert R6-S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB combivert R6-S and is the answer not in the manual?

KEB combivert R6-S Specifications

General IconGeneral
BrandKEB
Modelcombivert R6-S
CategoryPower Supply
LanguageEnglish

Related product manuals