1502756-02 - 141 -
DANGER
Danger of electric voltage!
Products with extraction power control (frequency inverters) are
intended for protection by line protection fuses.
If the product is operated on a mains supply with a residual current
circuit breaker (RCCB) connected upstream, the following must be
observed.
Since the operation of the frequency inverter on the protective earth
conductor can cause a direct current, the residual current circuit breaker
(RCCB) connected in series with the mains must meet the following
requirements.
Category
type:
Rated current
Tripping fault
current
Note
B
40125 A
300 mA
short time-
delayed
Tab. 57: Requirements for residual current circuit breaker
Example: Cable laying for the extraction capacity regulation