EasyManuals Logo

Kidde Fire Systems PEGAsys LV User Manual

Default Icon
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
April 200376-100016-002
PEGAsys LV
7-3
nection cable wire into its proper TB1 slot. Tighten the slot
screws firmly. See Figure 7-3 for a conduit to CCP ex-
ample. See Appendix B for recommended wiring.
Twisted, Unshielded
Wire
TB1
Enclosure
RX/TX
Module
Figure 7-3. Conduit to CCP
In retrofit applications where existing wiring will be used,
do not exceed the SLC resistance and capacitance limita-
tions listed above. All conduit and conductors must meet
NEC, NFPA-72 and any applicable local code requirements.
See Figure 7-4 for existing shielded cable termination. Op-
tionally, the PC line can be installed in a separate conduit
as shown previously, thus allowing the PC line to use
twisted, unshielded wire.
Grounding
Nut
Shielded
Wire
Enclosure
RX/TX
Module
TB1
Figure 7-4. Shielded Wire to CCP
Note: All new RCUs are shipped from Kidde with their
address set to 000. This address is reserved for
unregistered devices and cannot be used as a reg-
istered address. The unaddressed devices must
be connected to the RX/TX Module one at a time
in order to address them. Otherwise devices may
be pre-addressed or multiple pre-addressed loop
devices may be connected to the RX/TX PC line
at the same time using the hand-held device pro-
grammer (P/N 74-200013-001) .
Refer to Table 5-2 for a list of the types of allowable con-
figurations that can be selected, along with the respective
jumper settings for those configurations. As described in
this chapter, the PC line can be configured in Style 4, 6
or 7. Each Style is represented in Figures 7-5 through 7-8.
Style 4 configurations allow T-tapping. T-tapping is only
limited by sound installation techniques.
MODEL AI, N/O
INSTRUCTIONS
SEE INSTALLATION
CAT. NO. 70-407008-001
SmartOne
TM
FOR SERVICE SEND TO:
KIDDE-FENWAL, INC.
400 MAIN ST.
ASHLAND, MA 01721
DATE OF MANUFACTURE:
MAX. INSTALL. TEMP. 120°F
7654321
06-235578-001
PC PC PC PC
(+) (-) (+) (-)
8
A
SW
B
SW
(+)
LED
(-)
LED
ALLTERMINALS ARE POWER LIMITED
Addressable
Contact Input
Device
Detector Bases
T-Tap
TB1 of
RX/TX Module
Figure 7-5. Style 4, RX/TX PC Line Connections
In the Style 6 wiring configurations, the RX/TX automati-
cally transmits data and power bi-directionally when a break
in the PC line wiring occurs. If the break is in a single con-
ductor, all loop devices will remain fully operational. For
Style 6 PC line connections, if a PC line open trouble is
encountered, use the system reset switch on the display
and control board to reset the PC line to normal once the
fault is corrected.
MODEL AI, N/O
INSTRUCTIONS
SEE INSTALLATION
CAT.NO. 70-407008-001
SmartOne
TM
FOR SERVICE SEND TO:
KIDDE-FENWAL, INC.
400 MAIN ST.
ASHLAND, MA 01721
DATE OF MANUFACTURE:
MAX. INSTALL.TEMP. 120°F
7654321
06-235578-001
PC PC PC PC
(+) (-) (+) (-)
8
A
SW
B
SW
(+)
LED
(-)
LED
ALLTERMINALS ARE POWER LIMITED
TB1 of
RX/TX Module
Detector Bases
Addressable
Contact Input
Device
Figure 7-6. Style 6, RX/TX PC Line Connections

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems PEGAsys LV and is the answer not in the manual?

Kidde Fire Systems PEGAsys LV Specifications

General IconGeneral
BrandKidde Fire Systems
ModelPEGAsys LV
CategoryControl Unit
LanguageEnglish

Related product manuals