I-6August 1999 76-100016-001
PEGAsys
Intelligent Suppression Control/Fire Alarm System
RS232 PORT
FOR COMMUNICATION
WITH CCM.
NOTES:
1. SMART DEVICES MAY UTILIZE T-TAP WIRING METHOD IN
STYLE 4 CONFIGURATION ONLY.
2.
4. ARRANGEMENTS FOR PC LINE WIRING
PLUG IN THE LOOP ISOLATOR (RXTX) 74-200012-001
AND INTERCONNECT IT USING FLEX CABLES TO J3 ON
RXTX. MAKE SURE THAT UNEVEN PINS ARE
SIGNALING LINE CIRCUIT CHARACTERISTICS
MAX VOLTAGE:
MIN. VOLTAGE:
MAX. LINE CAPACITANCE:
MAX. LINE RESISTANCE:
MAX. NUMBER OF RCU'S:
MAX. RIPPLE VOLTAGE:
26.4 VDC
19.0 VDC
1.0 uF
26.0 OHMS
255
100 mV RMS
SMART DETECTORS USED:
PRODUCT NO'S. 70-401001-000
70-401004-000
71-401001-000
71-401004-000
70-402001-100
71-402001-100
70-404001-100
CONTACT INPUT DEVICES:
70-407004-001
70-407003-001
70-407002-00XPRODUCT NO'S.
RELAY OUTPUT DEVICES:
70-408003-000
70-408002-000PRODUCT NO.'S
LED 1 - RED LED INDICATES RXTX RESET WHEN ON.
LED 2 - GREEN LED INDICATES NORMAL OPERATION OF RXTX PC LINE
TRANSMITTER WHEN BLINKING.
SW 1 - CPU RESET.
SW 2 - PC LINE REST / DISCONNECT 24V FROM TERM. 2 & 3.
LOOP ISOLATORS:
PRODUCT NO.'S
RXTX 74-200012-001
ELECT. BOX 74-200012-002
BASE MOUNT 74-200012-004
MODULE
T1
KIDDE-FENWAL, INC.
RX/TX
76-100005-001
LED1
LED2
SW2
SW1
T1
J2
J1
12
1
J3
74-200012-001
TO FULLY UTILIZE LOOP ISOLATION FUNCTION.
STYLE 6 (4-WIRE) PC LINE CONFIGURATION IS RECOMMENDED
CAN BE INSTALLED ON PC LINE. NO MORE THAN 30 LOOP
MAXIMUM 20 LOOP ISOLATORS EXCLUDING ONE ON RX/TX3.
FROM POWER
24 VDC
SUPPLY
RX/TX
CPU RESET
PC LINE NORMAL
CPU RESET
PC LINE RESET
RX/TX ASSEMBLY
74-200005-001
ASHLAND, MA 01721
SHORT-2
SHORT-1
RX/TX
LOOP ISOLATOR
J3
JP2JP3
LOOP ISOLATOR
SEE NOTE 4
W2W1
SEE NOTE 4
34
4
21
MAXIMUM OF 255 LOOP DEVICES PER RX/TX
LOOP. ANY COMBINATION OF DEVICE TYPE
IS ACCEPTABLE.
DEVICES BETWEEN TWO ADJACENT LOOP ISOLATORS.
5. MAXIMUM OF ONE #12 AWG WIRE PER TERMINAL.
JUMPER
W1&W2
JP3
JP2
IN
IN
OPEN
STYLE 4
OPEN OUT
OPEN OUT
SHORTEDSHORTED
STYLE 6 w/LOOP ISO.
STYLE 7
4.1- STYLE SEVEN (7) REQUIRES THE USE OF LOOP
ISOLATORS, THE RXTX MODULE REQUIRES THE USE
OF ONE (1) P/N 74-200012-001 ISOLATOR MODULE
TO OPERATE IN THE STYLE 7 CONFIGURATION.
4.2- WHEN LOOP ISOLATOR USED:
INTERCONNECTED.
24 VDC
(RED)
RET
(BLK)
(OPTIONAL)
70-403001-XXX
70-407008-002
70-407008-001
70-408004-001
PRODUCT NO. 89-100081-001
ANALASER INTERFACE MODULE
STYLE 6
SHORTED
IN
IN
TITLE
Installation Wiring Diagram
Receiver/Transmitter Module
(PEGAsys)
DRAWING No.
06-235443-002
REVISION
AC
SHEET
1 of 2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems PEGAsys and is the answer not in the manual?

Kidde Fire Systems PEGAsys Specifications

General IconGeneral
BrandKidde Fire Systems
ModelPEGAsys
CategoryFire Alarms
LanguageEnglish

Related product manuals