A-1 August 199976-100016-001
Intelligent Suppression Control/Fire Alarm System
PEGAsys
APPENDIX A
POWER SUPPLY REQUIREMENTS
A-1 AC BRANCH CIRCUIT
The PEGAsys fire alarm/suppression control system requires connection to a separate dedicated AC branch circuit (120 or 240
VAC), which must be labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of the protected
premises. No other equipment may be powered from the fire-alarm branch circuit. The branch circuit wire must run continuously,
without any disconnect devices, from the power source to the fire alarm/suppression control panel. When multiple power supplies are
installed in the system enclosure(s) they must all be fed from the same circuit. Over-current protection for this circuit must comply with
Article 760 of the National Electric Code, NFPA-72 as well as applicable local codes. Use a minimum of # 14 AWG with 600-volt
insulation for this branch circuit.
Table A-1: AC Branch Circuit Requirements (120 VAC)
epyTeciveD
forebmuN
seciveD
warDtnerruC
)spmA(
tnerruClatoT
eciveDrep
lenaPlortnoC1X9.1=9.1
rewoPyrailixuA
roylppuS
eludoM
)(X9.1=
rofnmulocmuS
hcnarBCA
deriuqertnerruC
=spmA
NOTE: Each main power supply and power supply module added to the system would increase the AC requirement
by 1.9 Amps (max.)
Table A-2: AC Branch Circuit Requirements (220 VAC)
epyTeciveD
forebmuN
seciveD
warDtnerruC
)spmA(
tnerruClatoT
eciveDrep
lenaPlortnoC1X59.0=59.0
rewoPyrailixuA
ylppus
)(X59.0=
rofnmulocmuS
hcnarBCA
deriuqertnerruC
=spmA
NOTE: Each main power supply and power supply module added to the system would increase the AC requirement
by 0.95 Amps (max.)