FlexStat 8 Operation Guide, Rev. R
When BAC-1xxxxx models have an application with
the CO
2
sensor ANDthemodulatingeconomizer
optionenabled, menu items for DCV(Demand
ControlVentilation) will appear. Forinformation
abouttheDCVoptions,see (Advanced) CO2 Sensor
(and DCV) on page 11.
Fan Setup
FAN SETUP
SPEEDS:
OFF DELAY (SECS): 180
UNOCC: AUTO
OCC: AUTO
HTG FAN: AUTO
CONSTANT SPEED
For heating applications, Heating Fan is set to Auto
by default but can be disabled if needed (such as for
an FCU that is factory wired to run at a xed speed
or for a baseboard heater without a fan). The Heating
Fan selection is only available when the application
supports heating and either Occupied fan or Unoc-
cupied fan is set to Auto.
NOTE: For a Fan Fail Alarm, see Sensor Setup on
page 9 and Alarms on page 23.
Humidity Setup
HUMIDITY SETUP
DEHUMIDIFICATION
HUMIDIFICATION
DEHUMIDIFICATION
DEHUM:
ENABLE
NOTE: If a dehumidication option is enabled, the
Space Humidity Alarm will also be enabled.
See Alarms on page 23.
NOTE: To see the dehumidication option in the
Additional Setup menu for a HeatPump
application, select an Aux. Heat option
other than None (the default).
Motion Sensor Setup
MOTION SENSOR
OCC OVERRIDE:
STATE: OCCUPIED
STANDBY: DISABLE
—OFFSET: 3° F
—TIMER (MINS): 30
ENABLE
A motion/occupancy sensor may be enabled (the
default) to trigger occupancy override (enabled by
default, but only functional during scheduled o
times) and occupancy standby in relation to the
scheduled on and o times. (See the chart.)
During scheduled OFF (unoccupied) times,
temperature is controlled according to the seing of
the appropriate heat or cool setback (see Setpoints
on page 25). Occupancyoverride (for 1 hour as a
default) starts when the sensor detects motion.
Temperature will start being controlled according
to the appropriate setpoint. Occupancy override will
end (with the default seing) 1 hour after motion
was last detected. The length of occupancy override
is congurable in the System menu. See System
Modes on page 25.
During scheduled ON (occupied) times, temperature
is controlled according to the seing of the appro-
priate heat or cool setpoint. If enabled, occupancy
standby sets the temperature back or up (according
to the heating/cooling mode) by the Oset amount
when no motion is detected for the Timer amount (30
minutes by default). The normal setpoint is restored
when motion is detected twice (to reduce false detec-
tions) within three minutes.
NOTE: Occupancy standby, when activated, lets
the temperature go down or up (according
to the relevant mode) by the Oset amount
(3° by default), not the Setback seing in the
Setpoints menu (which usually has a larger
temperature dierential meant for a longer
o time).
NOTE: When the Advanced DCV mode is selected,
Standbyisenabledbydefaultandwhen
revertingfromStandbybacktoOccupied
mode,thesetpointisrestoredby1°every
15minutes—to further conserve energy
according to the guidelines by Portland
Energy Conservation, Inc. (PECI). In
BasicorStandard DCV mode or no DCV
is selected, the setpoint value is restored
by the full amount immediately when

Table of Contents

Other manuals for KMC Controls FlexStat

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KMC Controls FlexStat and is the answer not in the manual?

KMC Controls FlexStat Specifications

General IconGeneral
BrandKMC Controls
ModelFlexStat
CategoryThermostat
LanguageEnglish

Related product manuals