TP-6714 4/10 19Section 3 Operation
Section 3 Operation
3.1 Introduction
This section contains operation instructions, including:
D User interface panel, with display, pushbuttons, and
LED indicators
D Main screen
D System status, warnings, and faults
D Passwords
D Tes ts
D Warnings and Faults
D Reset Data
3.2 User Interface Panel
The user interface panel is located on the transfer switch
door. Figure 3-1 shows the user interface pushbuttons
and LED indicators.
3.2.1 Display
The four-line display indicates transfer switch status and
setup, including the following:
D System status
D Faults and warnings
D Active time delays
D Source voltages
D Source frequency (Hz)
D Current (amps)
D Source setup information
D Ti me and date
D Time and date of next scheduled exercise
The display also identifies the pushbutton functions,
which can change from screen-to-screen.
1. Source N Available LED
2. Source N Position LED
3. Source E Position LED
4. Source E Available LED
5. Display
6. Not in Auto LED
7. Pushbuttons (4)
8. System Alert LED
GM46892
8
1 2
3
4
6
7
5
Figure 3-1 User Interface Panel