TP-6714 4/1072 Section 5 Setup
Parameter Description Adjustment Range
Outputs
Assign Load Control Out # to each connected load output. Use
the Set Inputs/Outputs menu. See Section 5.12, programmable
Inputs and outputs.
Load Control Out 1--9
Load Control Mode
Select Current for current-based load control. See Section
5.10.2 for more information.
None/Time/Current
Loads to Control
Enter the number of loads to be controlled. Each load must be
connected to a separate output on the main logic board or
accessory I/O module.
1--9
High Current Level
If the current rises above this limit, loads will be removed in
order of their remove priority settings until the current falls back
to an acceptable level.
0--4000 Amps
Low Current Level
If the current drops below this level and some loads are not
connected, loads will be added in the order of their add priority
setting.
0--4000 Amps
Load Control # Enable/Disable
Enable or disable current-based load control for each load on
each source.
Enable or Disable
Add Priority
Assign a priority for the addition of each load when the current
level falls below the low current level. Add Priority #1 loads are
added first. The add priority and remove priority for a given load
canbedifferent.
1--9
Remove Priority
Assign a priority for the removal of loads when the current level
rises above the high current level. Remove priority #1 loads are
removed first. The add priority and remove priority for a given
load can be different.
1--9
Disconnect (Disc) Time Delay
Time delay after a transfer signal to allow disconnection of
selected loads before transfer to the other source. (Operates
when both sources are present.)
00:00 to 59:59
min:sec
Load Add Source1 or Source2
Time delay after the current falls below the low limit until the load
is added. Prevents load add caused by a momentary drop in
the current.
00:00 to 59:59
min:sec
Load Remove Src1 or Src2
Time delay after the current rises above the high limit until the
load is removed. Prevents load removal caused by a
momentary rise in the current.
00:00 to 59:59
min:sec
Figure 5-12 Current-Based Load Control Parameters