EasyManua.ls Logo

Laars FTCF140 - Zoning with Zone Valves

Laars FTCF140
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The FT Series Floor Standing, Combination Boiler
Page 45
(CH SUPPLY)
3/4" PIPE
(DHW OUTLET)
Backflow
preventer
3/4" PIPE
(DHW INLET)
(CH RETURN)
(DHW SUPPLY)
Circulation pump
Flow Check valve
Expansion tank
Air separator
Diaphragm Type
Pressure relief valve
Ball valve
Isolation valve
PRIMARY LOOP
(SPACE HEATING)
1”
Min
Piping
P
Make-Up Water
ZONE 1
ZONE 2
ZONE 3
Do not
exceed
12"
See
Note
SECONDARY LOOP
(SPACE HEATING)
Anti-scald rated
Mixing Valve
CAUTION
PRV (included) must be installed immediately at the
top of boiler outlet to PRV, with no valves between.
Refer to Section 4.15
__________________________________________
ATTENTION
PRV (inclus) doit être installé immédiatement en haut
de la chaudière sortie de PRV, sans les vannes entre.
Se reporter à la Section 4.15
__________________________________________
Auto Fill Valve
and Backow
Preventer Valves are
NOT included (Field
Supplied).
4.14.6 Zoning with Zone Valves
- In a valve based system, there is one circulator pump at the boiler and each heating zone has its own valve.
- Each thermostat is wired directly to the corresponding zone valve. Contacts in the zone valves provide a
proper signal to the boiler when the valve is opened.

Table of Contents

Related product manuals