EasyManuals Logo

Lamtec F200K User Manual

Lamtec F200K
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
17
4 Technical Data
Temperature - humidity - coupling 0 ... 95 % not condensing
Wear and tear parts none
Application in hazardous areas F200K .... Ex-II
Device group/category of
hazardous area, certificate
[Ex] II 3G, Zone 2,
[Ex] II 3D, Zone 22
IECEx IBE 15.0012X
Class I Division 2
File-No. E488138
Marking Ex nA nC IIC T6...T5 Gc X
Ex tc IIIC T85°C Dc X
Cl I Div2 Gr A T5
Standards IEC 60079-0, EN 60079-0
ANSI/ISA-12.12.01,
CAN/CSA C22.2 No. 213
Operating temperature range
Ambient temperature T5 -40°C/-40 °F ... Ta ... +75°C/+167 °F
T6 -40°C/-40 °F ... Ta ... +65°C/+149 °F
Additional Information Follow the section "Special Points to
Note When Using the Device in Explosion-
proof Areas".
Application in hazardous areas F200K .... Ex
Device group/category of
hazardous area, certificate
[Ex] II 2G, Zone 1
[Ex] II 2D, Zone 21
Certificate IECEx EPS 14.0042X,
EPS 14 ATEX 1 696 X
Marking Ex db IIC T6...T5 Gb
Ex tb IIIC T80°C, T95°C Db
Standards IEC 60079-0 , EN 60079-0
Operating Temperature range T5 -40 °C/-40 °F ... Ta ... +75 °C/+157 °F
(UV Version)
T6 -40 °C/-40 °F ... Ta ... +65 °C/+149 °F
(UV Version)
Ambient temperature T6-40 °C/-40 °F ... Ta ... +60 °C/+140 °F
(IR Version)
Additional information Follow the section "Special Points to note
when using the device in explosion-proof
areas".

Table of Contents

Other manuals for Lamtec F200K

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec F200K and is the answer not in the manual?

Lamtec F200K Specifications

General IconGeneral
BrandLamtec
ModelF200K
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals