7 Instructions on Commissioning and Maintenance
7.3 Troubleshooting
on apparently immaculate functioning according to the indicator elements
1 Check the output contact fuse and the contact
Disconnect the flame detector from the supply voltage
Check the normally closed output contact at the 1st clamping point behind the flame
detector between the brown (BR) and the white (WH) connection wire (avoid low re-
sistance continuity check - fuse 500 mA)
Connect the flame detector to the supply voltage
Check with simulated flame between the brown (BR) and the green (GN) connection
wire
2 Check the supply voltage
Connect the flame detector to the supply voltage
Check the supply voltage at the 1st clamping point behind the flame detector between
the red and the blue connection wire for compliance with the voltage limits (in particu-
lar the lower limit)
Repeat test with simulated flame
If the supply voltage is too low, this may be due to excessive lengths of the supply lines
which core sections are too small, apart from other faults.