7 Instructions on Commissioning and Maintenance
7.5 Maintenance
7.5.1 General Information
Provisions shall be made to ensure that the light entry port of the flame sensor and the viewing
port on the furnace, where the sensor is fitted, are regularly cleaned, i.e. at regular intervals,
which depend on the operating conditions of the furnace. The compact flame scanner needs
no maintenance. The operation of the flame scanner by physically shutting off the flame
should be incorporated into the maintenance cycle for the device.
NOTICE
If it is necessary to clean the optics of fiber optic flame detectors, special care should be taken
to clean the fiber optic surface. Damage to the surface can result in significant signal loss.
7.5.2 Instructions on Troubleshooting
DANGER!
The flame scanner is a safety device.
Any repair work or other changes to the device shall only be carried out by the manu-
facturer's specialist staff or by some other persons appointed by the manufacturer.
Any other person are not allowed to operate on parts inside the device.
In particular, this concerns the unauthorized exchange of the flame contact fuse.

Table of Contents

Other manuals for Lamtec F200K

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec F200K and is the answer not in the manual?

Lamtec F200K Specifications

General IconGeneral
BrandLamtec
ModelF200K
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals