7 Instructions on Commissioning and Maintenance
7.2.2 Special Points to Note When Using the Device in Explosion-proof Areas
The following applies when using the F200K Ex-II, F200K Ex in explosion-proof areas:
For use only in approved explosion protection zones.
To protect its aperture, only mount the F200K Ex-II, F200K Ex on a burner or boiler using
one of its holders: the FV30, FH30 or FS50.
Use only the types of cable specified by the manufacturer when extending cables.
When extending cables in the potentially explosive area, use only terminal housings that
are approved for this area. LAMTEC recommends the connection housing FG24 Ex for
this purpose.
Check if cable connections fit tightly. Should there be a need to loosen the cable connec-
tion, it is to be ensured that the cables do not turn while loosening and tightening the cable
connection.
Note, in particular, the information on setup in EN 60079-14, section 12.2 (cables and
earthing).
Only remove the connector of the F200K Ex-II, F200K Ex or any other cable connections
when it is deenergised.
See the warning on the device:
WARNING – DO NOT DISCONNECT WHEN ENERGISED.
In particular, seperation has to be in accordance with EN 60079-14 'Appendix:
Instructions for procedures to work safely in an explosive gas atmosphere', only permitted
after the release by personnel in charge of the explosion protection of the operating
company.
Opening the device is required during commissioning!
Should there be any risk of danger to the surroundings in an opened device, a clearance
measurement as described above should be done before the opening.
A transformer for generating the supply voltage must be carried out according to
IEC 61558-2-6.
You must use a current limiter with a limit on the rated voltage.
When using the device in the ambient temperature range, you must keep the temperature
in accordance with the temperature class:
See Ex marking on the device
If devices are so damaged that they no longer meet the requirements of the protection
class, you must replace them.
Special instructions for use in Hazardous Area Class I Division 2 (valid for F200K Ex-II)
During installation, the rules of the NEC (National Electrical Code) must be considered.
UL Listed Version:
The plug of the connecting cable must be secured against self-loosening after mounting
on the flame detector. There are screws on the union nut of the connector.

Table of Contents

Other manuals for Lamtec F200K

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec F200K and is the answer not in the manual?

Lamtec F200K Specifications

General IconGeneral
BrandLamtec
ModelF200K
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals