SPECIFICATIONS - BELT DRIVE BLOWER TWO-SPEED - 6 TON
General Data Nominal Tonnage 6 Ton 6 Ton
Model No. KGB074S4T KGB074H4T
E󰀩ciency Type Standard High
Blower Type  
Cooling
Performance
  
1
  
 2100 2100
2
Sound Rating Number (dBA) 79 79
 6.1 5.7
1
IEER 15.0 16.0
1
 11.2 12.0
Refrigerant

Refrigerant Type R-410A R-410A
Environ™ Coil System 7 lbs. 2 oz. 7 lbs. 2 oz.
Conventional Fin/Tube Coil 14 lbs. 8 oz. - - -
Humiditrol
®
 14 lbs. 11 oz. - - -
Gas Heating Options Standard (1 or 2 Stage),
Medium (1 or 2 Stage), or
High (1 or 2 Stage)
Standard (1 or 2 Stage),
Medium (1 or 2 Stage), or
High (1 or 2 Stage)
Compressor Type (one per unit)  
Outdoor Coil
Environ™
(Fin/Tube)
Net face area - sq. ft. 17.8 (19.3) 17.8
 1 (2) 1
 23 (20) 23
Outdoor
Coil Fan
Motor - (No.) HP (1) 1/3 (1) 1/3
Motor rpm 1075 1075
 375 375
Diameter - (No.) in. / No. of blades (1) 24 - 3 (1) 24 - 3
Total air volume - cfm 4700 4700
Indoor Coil Net face area - sq. ft. 9.72 9.72
Tube diameter - in. 3/8 3/8
 4 4
 14 14
Drain Connection (no.) and size - in. (1) 1 NPT (1) 1 NPT
Expansion device type 
3
Indoor

Selection
Nominal Motor Output  
Maximum Usable Motor Output (US Only)  
Motor - Drive Kit Number A04
968 - 1340 rpm
A08
1193-1591 rpm
AA01
522-784 rpm
AA02
632-875 rpm
AA03
798-1105 rpm
 (1) 10 x 10 (1) 15 x 9
Filters Type Disposable
Number and size - in. (4) 20 x 20 x 2 (4) 20 x 20 x 2
 

1

2

3




Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox KGB Series and is the answer not in the manual?

Lennox KGB Series Specifications

General IconGeneral
BrandLennox
ModelKGB Series
CategoryHeat Pump
LanguageEnglish

Related product manuals