BLOWER DATA
BELT DRIVE KIT SPECIFICATIONS - 036-074S
Model
No.
Motor HP No. of
Speeds
Drive Kits and RPM Range
Nominal Maximum A01 A02 A03 A04 A05 A06 A07 A08
036 1 1.15 1 673-1010 - - - - - - - - - 897-1346 - - - - - - - - -
2 2.3 1 673-1010 - - - - - - - - - 897-1346 - - - - - - - - -
048 1 1.15 1 - - - 745-1117 - - - - - - - - - 1071-1429 - - - - - -
2 2.3 1 - - - 745-1117 - - - - - - - - - 1071-1429 - - - - - -
060 1 1.15 1 - - - - - - 833-1250 - - - - - - - - - 1212-1548 - - -
2 2.3 1 - - - - - - 833-1250 - - - - - - - - - 1212-1548 - - -
074S 1 1.5 2 - - - - - - - - - 968-1340 - - - - - - - - - 1193-1591
2 2.3 2 - - - - - - - - - 968-1340 - - - - - - - - - 1193-1591
OPTIONS / ACCESSORIES AIR RESISTANCE FOR 024-074 MODELS - in. w.g.
Air Volume
cfm
Wet Indoor Coil Humiditrol Coil Gas Heat Economizer Filters
024-048 060 072/074 024-048 060, 074 Medium Input High Input MERV 8 MERV 13
800 0.01 0.01 0.01 0.00 0.00 0.02 0.02 0.04 0.04 0.05
1000 0.02 0.02 0.01 0.00 0.00 0.02 0.02 0.04 0.04 0.07
1200 0.03 0.04 0.02 0.01 0.00 0.02 0.02 0.04 0.04 0.07
1400 0.04 0.05 0.03 0.02 0.01 0.02 0.03 0.04 0.04 0.07
1600 0.05 0.06 0.04 0.03 0.02 0.03 0.04 0.04 0.04 0.07
1800 0.06 0.07 0.05 0.04 0.02 0.03 0.05 0.05 0.05 0.07
2000 0.08 0.09 0.06 0.04 0.03 0.04 0.06 0.05 0.05 0.08
2200 0.09 0.10 0.07 - - - 0.04 0.04 0.07 0.05 0.05 0.08
2400 0.10 0.12 0.08 - - - 0.04 0.05 0.08 0.05 0.05 0.08
2600 0.11 0.13 0.09 - - - 0.05 0.05 0.09 0.06 0.05 0.08
2800 0.13 0.15 0.10 - - - 0.05 0.06 0.10 0.06 0.05 0.08
3000 0.14 0.16 0.12 - - - 0.06 0.07 0.11 0.06 0.05 0.08
BELT DRIVE KIT SPECIFICATIONS - 072H/074H/090S
Model
No.
Motor HP No. of
Speeds
Drive Kits and RPM Range
Nominal Maximum AA01 AA02 AA03 AA04
072H 1 1.15 1 522-784 632-875 798-1105 - - -
2 2.3 1 522-784 632-875 798-1105 - - -
074H 1 1.15 2 522-784 632-875 798-1105 - - -
2 2.3 2 522-784 632-875 798-1105 - - -
090S4B 1 1.15 1 522-784 632-875 798-1105 - - -
2 2.3 1 522-784 632-875 798-1105 - - -
3 3.45 1 522-784 632-875 798-1105 921-1228
090S4T 2 2.3 2 522-784 632-875 798-1105 - - -



OPTIONS / ACCESSORIES AIR RESISTANCE FOR 090 MODELS - in. w.g.
Air Volume
cfm
Wet Indoor Coil Humiditrol Coil Gas Heat Economizer Filters
High Input MERV 8 MERV 13
2400 0.08 0.04 0.03 0.05 0.05 0.08
2600 0.09 0.05 0.04 0.06 0.05 0.08
2800 0.10 0.05 0.04 0.06 0.05 0.08
3000 0.11 0.06 0.04 0.06 0.05 0.08
3200 0.12 0.06 0.04 0.06 0.06 0.09
3400 0.14 0.07 0.05 0.06 0.06 0.09
3600 0.15 0.07 0.05 0.06 0.06 0.10