TABLE 10 580711-02
KGB/KCB048 Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
110 243 112 282 112 331 114 382 116 445 118 523
119 248 120 286 122 331 122 387 126 440 128 510
134 252 138 290 140 336 142 385 144 441 147 505
153 268 156 302 160 347 164 392 167 442 171 501
70
80
90
100
110
120
130
Liquid Temperature (° F)
Suction Pressure (psig)
Outdoor Temperature (°F)
KGB/KCB 048 Charging Curves
115°
105°
95°
85°
75°
65°
110 120 130 140 150 160 170100