TABLE 13 580791-01
KGB/KCB 074S & H Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
112 257 113 298 114 348 116 403 118 476 121 602
120 261 122 301 123 347 124 403 127 466 129 556
136 271 140 310 143 354 145 401 145 460 147 525
154 290 157 327 161 370 165 416 168 468 171 526
60
70
80
90
100
110
120
130
Liquid Temperature (° F)
Suction Pressure (psig)
Outdoor Temperature (°F)
KGB/KCB074S & H Charging Curves
115°
105°
95°
85°
75°
65°
110 120 130 140 150 160 170 180
580791-01