TABLE 9 580710-02
KGB/KCB036 Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
113 231 115 265 117 305 118 355 120 412 123 485
122 232 124 268 126 309 129 355 130 412 132 475
137 243 141 276 144 317 146 362 149 414 151 474
152 261 157 293 162 331 166 374 169 423 172 479
60
70
80
90
100
110
120
130
Liquid Temperature (° F)
Suction Pressure (psig)
Outdoor Temperature (°F)
KGB/KCB 036 Charging Curves
115°
105°
95°
85°
75°
65°
110 120 130 140 150 160 170 180
580710-02