Commissioning
Adjusting the motor
Motor temperature monitoring with PTC or thermal contact
6
6.6
6.6.3
6.6−10
EDSVF9383V EN 6.0−11/2009
Note!
ƒ In the Lenze setting the motor temperature monitoring is
switched off!
ƒ If you work with several parameter sets, the monitoring must
be activated separately in each parameter set!
1. Connect the monitoring circuit of the motor to T1 and T2.
– With 1.6kW < R < 4kW, the monitoring responds.
2. Set the controller reaction:
– C0585 = 3: Temperature monitoring of the motor is switched off.
– C0585 = 0: TRIP error message (display of keypad: OH8 )
– C0585 = 2: Warning signal (display of keypad: OH8 !)
Connect the PTC input with a fixed resistor:
ƒ R>4kW: The fault message OH8 must be activated.
ƒ R<1kW: Fault message must not be activated.
Activation
Function test