Commissioning
Operating mode
6
6.8
6.8−3
EDSVF9383V EN 6.0−11/2009
The frequency inverter is mainly designed for the applications listed in the
below table.
The table helps you to select the correct operating mode for your application:
ƒ C0006 = 5: V/f characteristic control with constant V
min
boost
ƒ C0006 = 1: Vector control
Power range 110 ... 400 kW
Selection of the operating mode in C0006
Motor cable
shielded £ 100 m
unshielded £ 200 m
Motor cable
shielded > 100 m
unshielded > 200 m
Applications with asynchronous
motors
recommended alternatively recommended alternatively
Single drives
Drives with constant load
5 1 5 −
Drives with heavy start
conditions
1 5 5 −
Travelling drives, conveyor belts 5 1 5 −
Pump drives, fan drives
1)
5 − 5 −
Extruder drives 5 1 5 −
Drives for wire drawing
machines
5 1 5 −
Drives for rolling machines 5 1 5 −
Drives for rewinders with
dancer
(speed−controlled)
1 5 − −
Group drives
(the resulting motor cable
length is decisive I
res
)
5 − 5 −
l
res
+ (i
Ǹ
@ (l
1
) l
2
) AAA ) l
i
))
1)
A square voltage characteristic (C0014 = 1) is recommended for this application
Note!
Only switch between the operating modes if the controller is
inhibited!
Recommended operating
modes