Safety instructions
General safety and application instructions for Lenze motors
2
2.2
2.2−2
EDSVF9383V EN 6.0−11/2009
Ensure an even surface, solid foot and flange mounting and exact alignment
if a direct clutch is connected. Avoid resonances with the rotational
frequency and double mains frequency which may be caused by the
assembly. Turn rotor by hand, listen for unusual slipping noises. Check the
direction of rotation when the clutch is not active (observe section "Electrical
connection").
Use appropriate means to mount or remove belt pulleys and clutches
(heating) and cover them with a touch guard. Avoid impermissible belt
tensions.
The machines are half−key balanced. The clutch must be half−key balanced,
too. The visible jutting out part of the key must be removed.
If required, provide pipe connections. Designs with shaft end at bottom must
be protected with a cover which prevents the ingress of foreign particles into
the fan. Free circulation of the cooling air must be ensured. The exhaust air
− also the exhaust air of other machines next to the drive system − must not
be taken in immediately.
All operations must only be carried out by qualified and skilled personnel on
the low−voltage machine at standstill and deenergised and provided with a
safe guard to prevent an unintentional restart.This also applies to auxiliary
circuits (e. g. brake, encoder, blower).
Check safe isolation from supply!
If the tolerances specified in EN 60034−1; IEC 34 (VDE 0530−1) − voltage ±5 %,
frequency ±2 %, waveform, symmetry − are exceeded, more heat will be
generated and the electromagnetic compatibility will be affected.
Observe the data on the nameplate, operating notes, and the connection
diagram in the terminal box.
The connection must ensure a continuous and safe electrical supply (no
loose wire ends); use appropriate cable terminals. The connection to the PE
conductor must be safe. The plug−in connector must be bolt tightly (to stop).
The clearances between blank, live parts and to earth must not fall below
8 mm at U
r
£ 550 V, 10 mm at U
r
£ 725 V, 14 mm at U
r
£ 1000 V.
The terminal box must be free of foreign particles, dirt and moisture. All
unused cable entries and the box itself must be sealed against dust and
water.