Configuration
Code table
8
8.5
8.5−45
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0725 Function 2
Function selection, function
block DIGDEL2
See System
Manual
(extension)
0 On delay On delay 1. LOW−HIGH edge at
DIGDEL2−IN starts a timing
element
2. After the time has elapsed
(C0726), DIGDEL2−OUT
switches to HIGH
1 Off delay Off delay 1. LOW−HIGH edge at
DIGDEL2−IN starts a timing
element and sets
DIGDEL2−OUT = HIGH
2. After the time has elapsed
(C0726), DIGDEL2−OUT
switches to LOW
2 ON/OFF delay On/off delay 1. LOW−HIGH or HIGH−LOW
edge at DIGDEL2−IN starts a
timing element
2. After the time has elapsed
(C0726),
DIGDEL2−OUT = DIGDEL2−IN
C0726 Delay T 1.000 0.001 {0.001 s} 60.000 Delay time, function block
DIGDEL2
C0728
CFG: IN 1000 FIXED0 Selection list 2 Configuration of digital input
signal, function block DIGDEL2
C0729 DIS: IN 0 1 Function block DIGDEL2
l Display of the signal linked in
C0728
C0730 Mode 0
0 Stop measurement
Function block OSZ
l Starting / stopping the
measured value recording
See System
Manual
(extension)
1 Start measurement
C0731 Status
0 Measurement completed
Oscilloscope function
l Read only
l Current operating status
1 Measurement active
2 Trigger detected
3 Abort
4 Abort after trigger
5 Read memory
C0732
Selection list 1
Configuration of analog input
signals, function block OSZ
Function block OSZ
See System
Manual
(extension)
1 OSZ channel 1 1000 FIXED0%
2 OSZ channel 2 1000 FIXED0%
3 OSZ channel 3 1000 FIXED0%
4 OSZ channel 4 1000 FIXED0%
C0733
Selection list 2
Configuration of digital input
signal, function block OSZ
1 Trigger input 1000 FIXED0