EasyManua.ls Logo

Lenze 9300 vector - Page 88

Lenze 9300 vector
466 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring of the standard device
Basic devices in the power range 250 ... 400 kW
Master and slave connection
5
5.4
5.4.2
5.4−5
EDSVF9383V EN 6.0−11/2009
Connection of the control cables between master and slave
DC+
DC-
0
2
1
1
0
4
0
5
1
3
9300VEC028
Fig. 5.4−4 Connection of the control cables between master and slave
1. Installation and connection of the ribbon cable :
By default the ribbon cable is inside the master. The plug is already
attached to the Drive Board.
Route the ribbon cable from the master to the Drive Board
connection in the slave, inserting the ribbon cable into the cable
ducts .
Plug the ribbon cable plug into the socket at the Drive Board.
2. Laying and connecting 2−core cables with plugs :
By default the cable is inside the master. The corresponding cable with
socket is in the slave.
Lay the two−core cable from the master to the socket in the slave.
Connect the 2−pole plug with the 2−pole socket in the slave.
3. Laying and connecting 10−core cables with plugs :
By default the cable is inside the master. The corresponding cable with
socket is in the slave.
Lay the two−core cable from the master to the socket in the slave.
Connect the 10−pole plug with the 10−pole socket in the slave.
How to connect the control
cables
efesotomasyon.com - Lenze

Table of Contents

Other manuals for Lenze 9300 vector

Related product manuals