Electrical installation
Mains connection
Fuses and cable cross−sections according to UL
5
125
EDK82EV222 DE/EN/FR 13.0
Rated fuse current / cable cross−section8200 vector
Circuit−breakerFuse
8200 vector
L1, L2, L3, N, PETypeL1, L2, L3, N, PEType
[AWG][A][AWG][A]Type
Mains 1/N/PE AC 230/240 V − operation with mains choke/mains filter
E82xV251K2C
10 16 15
14
4)
E82xV371K2C 10 16 15
14
4)
E82xV551K2C 10 16 15
14
4)
E82xV751K2C 15 14 15
14
4)
E82xV152K2C 20 2 x 16 25
2 x 14
4)
E82xV222K2C 20 2 x 16 30
2 x 14
4)
Mains 3/PE AC 230/240 V − operation without mains choke/mains filter
E82xV551K2C 6 18 15
14
4)
E82xV751K2C 10 16 15
14
4)
E82xV152K2C 15 14 15
14
4)
E82xV222K2C 15 2 x 16 20
2 x 14
4)
Mains 3/PE AC 230/240 V − operation with mains choke/mains filter
E82xV551K2C 6 18 15
14
4)
E82xV751K2C 10 16 15
14
4)
E82xV152K2C 15 14 15
14
4)
E82xV222K2C 15 2 x 16 20
2 x 14
4)
Mains 3/PE AC 400/500 V − operation without mains choke/mains filter
E82xV551K4C
6 18 15
14
4)
E82xV751K4C
6 18 15
14
4)
E82xV152K4C
10 16 15
14
4)
E82xV222K4C
10 16 15
14
4)
Mains 3/PE AC 400/500 V − operation with mains choke/mains filter
E82xV551K4C
6 18 15
14
4)
E82xV751K4C
6 18 15
14
4)
E82xV152K4C
10 16 15
14
4)
E82xV222K4C
10 16 15
14
4)
4)
Pin−end connector required