EasyManuals Logo

Lenze E82EV User Manual

Lenze E82EV
Go to English
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #103 background imageLoading...
Page #103 background image
Technical data
Rated data
Operation with rated power (normal operation)
3
103
EDK82EV222 DE/EN/FR 13.0
Rated data
Operation with rated power (normal operation)
For data for operation at rated mains voltage and switching frequency 8 kHz, sin. data and restrictions
for other switching frequencys see system manual.
Type
Power
Rated mains voltage
Mains current [A] Output current [A] Earth
[kW] without with
I
rated
I
max
(60 s)
1)
[kg]
P
rated
Mains choke
E82EV251K2C
3)
0.25
1/N/PE AC 230/240 V:
180 V −0 % ... 264 V +0 %
45 Hz −0 % ... 65 Hz +0 %
DC 325 V:
260 V −0 % ... 370 V +0 %
3.4 3.0 1.7 2.5
0.8
(E82CV... 0.6)
E82EV371K2C
3)
0.37 5.0 4.2 2.4 3.6
E82EV551K2C 0.55 6.0 5.6 3.0 4.5
1.2
(E82CV... 0.9)
E82EV751K2C 0.75 9.0 7.5 4.0 6.0
E82EV152K2C 1.5 15.0 12.5 7.0 10.5
1.6
(E82CV... 1.1)
E82EV222K2C
2)
2.2 18.0 9.5
(E82CV... 8.5)
14.2
E82EV551K2C 0.55
3/PE AC 230/240 V:
180 V −0 % ... 264 V +0 %
45 Hz −0 % ... 65 Hz +0 %
DC 325 V:
260 V −0 % ... 370 V +0 %
3.9 2.7 3.0 4.5
1.2
(E82CV... 0.9)
E82EV751K2C 0.75 5.2 3.6 4.0 6.0
E82EV152K2C 1.5 9.1 6.3 7.0 10.5
1.6
(E82CV... 1.1)
E82EV222K2C
2)
2.2 9.0 9.5
(E82CV... 8.5)
14.2
E82EV551K4C 0.55
3/PE AC 400 V:
320 V −0 % ... 440 V +0 %
45 Hz −0 % ... 65 Hz +0 %
DC 565 V:
450 V −0 % ... 620 V +0 %
2.5 2.0 1.8 2.7
1.2
(E82CV... 0.9)
E82EV751K4C 0.75 3.3 2.3 2.4 3.6
E82EV152K4C 1.5 5.5 3.9 3.9 5.9
1.6
(E82CV... 1.1)
E82EV222K4C 2.2 7.3 5.1 5.6 8.4
E82EV551K4C 0.55
3/PE AC 500 V:
400 V −0 % ... 550 V +0 %
45 Hz −0 % ... 65 Hz +0 %
DC 710 V:
565 V −0 % ... 775 V +0 %
2.0 1.4 1.4 2.7
1.2
(E82CV... 0.9)
E82EV751K4C 0.75 2.6 1.8 1.9 3.6
E82EV152K4C 1.5 4.4 3.1 3.1 5.9
1.6
(E82CV... 1.1)
E82EV222K4C 2.2 5.8 4.1 4.5 8.4
1)
Currents for periodic load change: 1 min overcurrent time with I
max
and 2 min base load time with 75 % I
r
2)
Operation only permitted with mains choke ( 120)
3)
DC supply not possible
Operation with increased rated power
System Manual

Table of Contents