Commissioning
Configuring the host system (master)
Setting compatibility with PPO types1 ... 5
6
l
30
EDS82ZAFPC201 EN 4.0
6.3.1 Setting compatibility with PPO types1 ... 5
Process data assignment of PPO types:
Type Selection text in LENZ08IB.GSE
PPO1
PKW (cons)
+ PZD (2 words)
PKW (cons)
+ PZD (2 words cons)
PPO2
PKW (cons) + PZD (6 words)
PKW (cons) + PZD (6 words cons)
PPO3
PZD (2 words)
PZD (2 words cons)
PPO4
PZD (6 words)
PZD (6 words cons)
PPO5
PKW (cons) + PZD (10 words)
PKW (cons) + PZD (10 words cons)
) Note!
In order to provide compatibility with the PPO types1...5 (PROFIdrive device
control), the following codes must be configured in addition:
ƒ C1510/1 = 20 (PROFIdrive status word)
ƒ C1511/1 = 19(PROFIdrive control word)
Example 1
The slave is to operate with PPO2 and consistent process data.
1. Select the entry "PKW(cons)+PZD(6W cons)" from the GSE file.
2. Set the following codes via the parameter data channel:
– C1510/1 = 20
– C1511/1 = 19
3. Set C1511/1 = 65535 to enable the process output words.
Example 2
The slave is to operate with PPO4 and inconsistent process data.
1. Select the entry "PZD(6W)" from the GSE file.
2. Set the following codes via the parameter data channel:
– C1510/1 = 20
– C1511/1 = 19
3. Set C1511/1 = 65535 to enable the process output words.