Disregarding the following basic safety measures and safety informaon may lead to severe personal injury
and damage to property!
Observe all specicaons of the corresponding documentaon supplied. This is the precondion for safe
and trouble-free operaon and for obtaining the product features specied.
Please observe the specic safety informaon in the other secons!
DANGER!
Electrical voltage
P
ossible consequences: Death or severe injuries
▶
Any work on the inverter must only be carried out in the deenergised state.
▶
Inverter up to 45 kW: Aer switching o the mains voltage, wait for at least 3 min before you start
working.
▶
Inverter from 55 kW onwards: Aer switching o the mains voltage, wait for at least 10 min before you
start working.
Basic safety instrucons
DANGER!
Dangerous electrical voltage
Dea
th or severe injuries from electric shock.
▶
Any work on the inverter must only be carried out in a deenergized state.
▶
Aer switching o the mains voltage, observe the signs on the product.
Personnel
The product must only be used by qualied personnel. IEC 60364 or CENELEC HD 384 dene the skills of
these per
sons:
•
They are familiar with installing, mounng, commissioning, and operang the product.
•
They have the corresponding qualicaons for their work.
•
They know and can apply all regulaons for the prevenon of accidents, direcves, and laws applicable at
the place of use.
Process engineering
The procedural notes and circuit details described are only proposals. It is up to the user to check whether
they can be adapted to the parcular applicaons. Lenze does not take any responsibility for the suitability
of the procedures and circuit proposals described.
Device protecon
•
The ma
ximum test voltage for
insulaon tests between a control potenal of 24 V and PE must not
exceed 110 V DC (EN 61800−5−1).
Safety instrucons
Basic safety
instrucons
112