POWERLINK
Typical topologies
Line
CN2n
CN22
CN21
CN1n
CN12
CN11
H2
H1
MN
MN Managing Node H Hub
CN Controlled Node
Bus-related informaon
Name Ethernet POWERLINK
Communicaon medium Ethernet 100 Mbps, half duplex
Use Connecon of the inverter to a
PO
WERLINK network
Connecon system RJ45
Status display 2 LEDs
Connecon designaon IN: X286
OUT: X287
Status displays at the RJ45 sockets
The LEDs at the RJ45 sockets indicate the connecon status to the network:
LED (green) Status/meaning
o No
connecon to the network.
on
A physical connecon to the network is available.
ickers
Data is exchanged via the network.
LED (red) Status/meaning
on
POWERLINK collision
Basic network sengs
The rotary encoder switch allows you to set the node address (last byte of the IP address).
Seng Node address Resulng IP address
0x00 Value from parameter 192.168.100.<parameter value>
0x01 ... 0xEF Switch posion 192.168.100.<switch
posion>
Electrical installaon
Networks
PO
WERLINK
177