Terminal data
Inverter I55AExxxx
Inverter kW 0.25 ... 0.75 1.1 ... 2.2 0.25 ... 2.2 0.25 ... 2.2
Connecon Mains connecon X100 PE connecon Motor connecon
X105
Connecon type Pluggable screw terminal PE screw Pluggable screw
terminal
Max. cable cross-secon mm² 2.5 6 6 2.5
Stripping length mm 8 8 10 8
Tightening torque Nm 0.5 0.7 2 0.5
Required tool 0.5 x 3.0 0.6 x 3.5 Torx 20 0.5 x 3.0
Fusing data
EN 60204-1
Inverter Fuse Circuit breaker Earth-leakage circuit
breaker
Characterisc Max. rated
current
Characterisc Max. rated
current
A A
I55AE125B gG/gL or gRL 10 B 10 ≥ 30 mA, type A or B
I55AE125D gG/gL or gRL 10 B 10 ≥ 30 mA, type A or B
I55AE137B gG/gL or gRL 10 B 10 ≥ 30 mA, type A or B
I55AE137D gG/gL or gRL 10 B 10 ≥ 30 mA, type A or B
I55AE155B gG/gL or gRL 16 B 16 ≥ 30 mA, type A or B
I55AE155D gG/gL or gRL 16 B 16 ≥ 30 mA, type A or B
I55AE175B gG/gL or gRL 16 B 16 ≥ 30 mA, type A or B
I55AE175D gG/gL or gRL 16 B 16 ≥ 30 mA, type A or B
I55AE211B gG/gL or gRL 25 B 25 ≥ 30 mA, type A or B
I55AE211D gG/gL or gRL 25 B 25 ≥ 30 mA, type A or B
I55AE215B gG/gL or gRL 25 B 25 ≥ 30 mA, type A or B
I55AE215D gG/gL or gRL 25 B 25 ≥ 30 mA, type A or B
I55AE222B gG/gL or gRL 25 B 25 ≥ 30 mA, type A or B
I55AE222D gG/gL or gRL 25 B 25 ≥ 30 mA, type A or B
Electrical installaon
Mains connecon
1-phase mains connecon 230/240 V
157