Terminal data
Inverter I55AExxxF
Inverter kW 0.37 ... 2.2 3.0 ... 4.0 5.5 7.5 ... 11 15 ... 22 30 ... 45
Connecon Mains connecon X100
Connecon type Pluggable
screw
terminal
Screw terminal
Max. cable cross-secon mm² 2.5 6 6 16 35 50
Stripping length mm 8 9 9 11 18 19
Tightening torque Nm 0.5 0.5 0.5 1.2 3.8 4
Required tool 0.5 x 3.0 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5 Hexagon
socket 5
Inverter I55AExxxF
Inverter kW 55 ... 75 90 ... 110 0.37 ... 5.5 3.0 ... 4.0 7.5 ... 11 15 ... 75
Connecon Mains connecon X100 PE connecon
Connecon type Screw terminal PE screw
Max. cable cross-secon mm² 95 150 6 6 16 25
Stripping length mm 22 28 10 10 11 16
Tightening torque Nm 10 18 2 2 3.4 4
Required tool Hexagon
socket 6
Hexagon
socket 8
Torx 20 PZ2
Inverter I55AExxxF
Inverter kW 90 ... 110 0.37 ... 2.2 3.0 ... 4.0 5.5 7.5 ... 11 15 ... 22
Connecon PE connecon Motor connecon X105
Connecon type PE bolt Pluggable
screw
terminal
Screw terminal
Max. cable cross-secon mm² 150 2.5 6 6 16 35
Stripping length mm - 8 9 9 11 18
Tightening torque Nm 10 0.5 0.5 0.5 1.2 3.8
Required tool Width AF 13 0.5 x 3.0 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5
Inverter I55AExxxF
Inverter kW 30 ... 45 55 ... 75 90 ... 110
Connecon Motor connecon X105
Connecon type Screw terminal
Max. cable cross-secon mm² 50 95 150
Stripping length mm 19 22 28
Tightening torque Nm 4 10 18
Required tool Hexagon socket 5 Hexagon socket 6 Hexagon socket 8
Inverter I55BExxxF
Inverter kW 3.0 ... 4.0 3.0 ... 4.0 3.0 ... 4.0
Connecon Mains connecon X100 PE connecon Motor connecon X105
Connecon type Pluggable screw terminal PE screw Pluggable screw terminal
Max. cable cross-secon mm² 4 6 2.5
Stripping length mm 8 10 8
Tightening torque Nm 0.6 2 0.5
Required tool 0.5 x 3.0 Torx 20 0.5 x 3.0
Electrical
installaon
Mains connecon
3-phase mains connecon 400 V
162