Terminal data
Inverter I55AExxxA
Inverter kW 0.25 ... 0.37 0.75 ... 1.1 0.25 ... 1.1 0.25 ... 1.1
Connecon Mains connecon X100 PE connecon Motor connecon
X105
Connecon type Pluggable screw terminal PE screw Pluggable screw
terminal
Max. cable cross-secon mm² 2.5 6 6 2.5
Stripping length mm 8 8 10 8
Tightening torque Nm 0.5 0.7 2 0.5
Required tool 0.5 x 3.0 0.6 x 3.5 Torx 20 0.5 x 3.0
Fusing data
EN 60204-1
Inverter Fuse Circuit breaker Earth-leakage circuit
breaker
Characterisc Max. rated
current
Characterisc Max. rated
current
A A
I55AE125A gG/gL or gRL 16 B 16 ≥ 30 mA, type A or B
I55AE137A gG/gL or gRL 16 B 16 ≥ 30 mA, type A or B
I55AE175A gG/gL or gRL 25 B 25 ≥ 30 mA, type A or B
I55AE211A gG/gL or gRL 25 B 25 ≥ 30 mA, type A or B
Electrical
installaon
Mains connecon
1-phase mains connecon 120 V