Fusing data
EN 60204-1
Inverter Fuse Circuit breaker Earth-leakage circuit
breaker
Characterisc Max. rated
current
Characterisc Max. rated
current
A A
I55AE137F gG/gL or gRL 10 B 10 ≥ 30 mA, type B
I55AE155F gG/gL or gRL 10 B 10 ≥ 30 mA, type B
I55AE175F gG/gL or gRL 10 B 10 ≥ 30 mA, type B
I55AE211F gG/gL or gRL 16 B 16 ≥ 30 mA, type B
I55AE215F gG/gL or gRL 16 B 16 ≥ 30 mA, type B
I55AE222F gG/gL or gRL 16 B 16 ≥ 30 mA, type B
I55AE230F gG/gL or gRL 25 B 25 ≥ 300 mA, type B
I55BE230F gG/gL or gRL 25 B 25 ≥ 30 mA, type B
I55AE240F gG/gL or gRL 25 B 25 ≥ 300 mA, type B
I55BE240F gG/gL or gRL 25 B 25 ≥ 30 mA, type B
I55AE255F gG/gL or gRL 25 B 25 ≥ 300 mA, type B
I55AE275F gG/gL or gRL 32 B 32 ≥ 300 mA, type B
I55AE311F gG/gL or gRL 32 B 32 ≥ 300 mA, type B
I55AE315F gG/gL or gRL 63 B 63 ≥ 300 mA, type B
I55AE318F gG/gL or gRL 63 B 63 ≥ 300 mA, type B
I55AE322F gG/gL or gRL 63 B 63 ≥ 300 mA, type B
I55AE330F gG/gL or gRL 80 B 80 ≥ 300 mA, type B
I55AE337F gG/gL or gRL 100 B 100 ≥ 300 mA, type B
I55AE345F gG/gL or gRL 125 B 125 ≥ 300 mA, type B
I55AE355F gR 160 - - ≥ 300 mA, type B
I55AE375F gR 160 - - ≥ 300 mA, type B
I55AE390F gR 300 - - ≥ 300 mA, type B
I55AE411F gR 300 - - ≥ 300 mA, type B
Electrical
installaon
Mains connecon
3-phase mains connecon 480 V