3-phase mains connecon 480 V "Light Duty"
Rated data
The output currents apply to these operang condions:
•
A
t a switching frequency of 2 kHz or 4 kHz: Ambient temperature above 40 °C with a rated output current
reduced by 2.5 %/°C.
•
If the load characterisc "Light Duty" and the switching frequencies 8 kHz or 16 kHz are selected, only the
v
alues of the load characterisc "Heavy Duty" are reached.
Inverter I55AE230F I55BE230F I55AE240F I55BE240F I55AE255F I55AE275F I55AE311F
Rated power kW 4 4 5.5 5.5 7.5 11 15
Rated power hp 5 5 7.5 7.5 10 15 20
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-400/480 V
Rated mains current
Without mains choke A 8.6 8.6 11.2 11.2 15.3 22 -
With mains choke A 6.8 6.8 8.8 8.8 12.1 17.2 22.6
Apparent output power kVA 5.9 5.9 8 8 10.5 15 19
Rated output current
2 kHz A 7.6 7.6 9.8 9.8 13.2 18.3 25.2
4 kHz A 7.6 7.6 9.8 9.8 13.2 18.3 25.2
8 kHz A - - - - - - -
16 kHz A - - - - - - -
Power loss
2 kHz W 94 94 125 125 163 238 290
4 kHz W 100 100 133 133 173 253 309
8 kHz W - - - - - - -
16 kHz W - - - - - - -
For controller inhibit W 6 6 6 6 6 6 6
Cyclic mains switching 3 mes per minute
Max. motor cable length
shielded
Without EMC category m 100 50 100 50 100 100 100
Category C1 (2 kHz, 4 kHz, 8
kHz)
m - - - - - - -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20 20 20 20 20 20 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 35 35 35 35 35 50 50
Weight kg 2.3 1.35 2.3 1.35 2.3 3.7 3.7
Weight lb 5 3 5 3 5 8 8
Technical data
3-phase mains connecon 480 V "Light Duty"
Ra
ted data
208