EasyManua.ls Logo

Lenze i550 Series - Technical Data; Standards and Operating Conditions; Conformities;Approvals; Protection of Persons and Device Protection

Lenze i550 Series
212 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
Standards and operang condions
Conformies/approvals
Conformity
CE
2014/35/EU Low-Voltage Direcve
2014/30/EU EMC Direcve (reference: CE-typical drive system)
EAC
TR CU 004/2011 Eurasian conformity: safety of low voltage equipment
TR CU 020/2011
Eurasian conformity: electromagnec compability of
technical means
RoHS 2011/65/EU
Restricons on the use of certain hazardous substances in
electrical and electronic devices
Approval
UL UL 61800-5-1
for USA and Canada (requirements of the CSA 22.2 No.
274)
File No. E132659
Protecon of persons and device protecon
Degree of protecon
IP20 EN 60529
Data applies for operaonally ready mounted state and not
in wire range of terminals
UL 50 Protecon against accidental contact only
Open type Only in UL-approved systems
Insulaon resistance
Overvoltage category III EN 61800-5-1 0 … 2000 m amsl
Overvoltage category II EN 61800-5-1 over 2000 m amsl
Isolaon of control circuits
Safe mains isolaon via double/reinforced
insulaon
EN 61800-5-1
Leakage current
> 3.5 mA AC, > 10 mA DC EN 61800-5-1 Please observe regulaons and safety instrucons!
Starng current
≤ 3 x rated mains current
Protecve measures against
Short circuit
Earth fault Earth-fault protected depending on operang status
Overtemperature of motor PTC or thermal contact, I²xt monitoring
Overvoltage
Motor stalling
EMC data
Noise emission
Category C1 EN 61800-3 See rated data
Category C2 EN 61800-3 See rated data
Category C3 EN 61800-3 See rated data
Noise immunity
Fullls requirements according to EN 61800-3
Operaon on public supply systems
Take measures to limit the expected radio
interference:
The machine or system manufacturer is responsible for
compliance with the requirements for the machine/system!
< 1 kW: With mains choke
EN 61000-3-2
> 1 kW for mains current ≤ 16 A: Without
addional measures
Mains current > 16 A: with mains choke
or mains lter, with dimensioning for
rated power.
EN 61000-3-12
Technical data
EMC da
ta
188

Table of Contents

Other manuals for Lenze i550 Series

Related product manuals