Inial switch-on and funconal test
Target: achieve rotaon of the motor connected to the inverter as quickly as possible.
Requirements:
•
The connected motor matches the inverter in terms of power.
•
The parameter sengs comply with the delivery status (Lenze seng).
1. Preparaon
1. Wire power terminals.
2. Wire digital inputs X3/DI1 (start/stop), X3/DI3 (reversal) and X3/DI4 (frequency preset 20 Hz).
3. Do not connect terminal X3/AI1 (analog setpoint selecon) or connect it to GND.
Start/
Stop
DI1
DI3
DI4
24V
X3
20 Hz
2. Switch on mains and check readiness for operaon
1. Switch on mains voltage.
2. Observe LED status displays "RDY" and "ERR" on the front of the inverter:
a) If the blue "RDY" LED is blinking and the red "ERR" LED is o, the inverter is ready for operaon. The
controller is inhibited.
You can now start the drive.
b) If the red "ERR" LED is lit permanently, a fault is pending.
Eliminate the fault before you carry on with the funconal test.
LED status displays
"RDY" LED (blue) "ERR" LED (red) Status/meaning
o o No supply voltage.
blinking (1 Hz) o Safe torque o (STO) acve.
blinking fast (4 Hz) Safe torque o (STO) acve. Warning acve.
blinking (2 Hz) o Inverter inhibited.
lit every 1.5 s for a
short me
Inverter inhibited, no DC-bus voltage.
blinking fast (4 Hz) Inverter inhibited, warning acve.
on Inverter inhibited, fault acve.
on o Inverter enabled. The motor rotates according to the
setpoint specied or quick stop acve.
blinking fast (4 Hz) Inverter enabled, warning acve.
blinking (1 Hz) Inverter enabled, quick stop as response to a fault acve.
Commissioning
Inial switch-on and funconal test
186