NOTICE
▶
UL marking
▶
Internal overload protecon rated for 125 % of the rated FLA.
▶
Marquage UL
▶
Protecon contre les surcharges conçue pour se déclencher à 125 % de l'intensité assignée à pleine
charge.
Branch Circuit Protecon (BCP) with Short Circuit Current Rangs (SCCR) with Standard Fuses. (Tested per
UL61800-5-1, reference UL le E132659)
These devices are suitable for motor group installaon when used with Standard Fuses. For single motor
installaon, if the fuse value indicated is higher than 400% of the motor current (FLA), the fuse value has to
be calculated. If the value of the fuse is below two standard rangs, the nearest standard rangs less than
the calculated value shall apply.
Inverter Standard Fuses (UL248)
Mains kW hp SCCR
Max. rated
current
Class
120 V, 1-ph 0.25 0.33 5 kA 15 A CC
120 V, 1-ph 0.37 0.50 5 kA 15 A CC
120 V, 1-ph 0.75 1.00 5 kA 30 A CC, J, T
120 V, 1-ph 1.10 1.50 5 kA 30 A CC, J, T
230 V, 1-ph 0.25 0.33 65 kA 15 A CC
230 V, 1-ph 0.37 0.50 65 kA 15 A CC
230 V, 1-ph 0.55 0.75 65 kA 15 A CC
230 V, 1-ph 0.75 1.00 65 kA 15 A CC
230 V, 1-ph 1.10 1.50 65 kA 30 A CC, J, T
230 V, 1-ph 1.50 2.00 65 kA 30 A CC, J, T
230 V, 1-ph 2.20 3.00 65 kA 30 A CC, J, T
230 V, 1/3-ph 0.25 0.33 65 kA 15 A CC
230 V, 1/3-ph 0.37 0.50 65 kA 15 A CC
230 V, 1/3-ph 0.55 0.75 65 kA 15 A CC
230 V, 1/3-ph 0.75 1.00 65 kA 15 A CC
230 V, 1/3-ph 1.10 1.50 65 kA 30 A CC, J, T
230 V, 1/3-ph 1.50 2.00 65 kA 30 A CC, J, T
230 V, 1/3-ph 2.20 3.00 65 kA 30 A CC, J, T
230 V, 3-ph 4.00 5.00 100 kA 40 A J, T
230 V, 3-ph 5.50 7.50 100 kA 40 A J, T
480 V, 3-ph 0.37 0.50 65 kA 15 A CC
480 V, 3-ph 0.55 0.75 65 kA 15 A CC
480 V, 3-ph 0.75 1.00 65 kA 15 A CC
480 V, 3-ph 1.1 1.5 65 kA 15 A CC
480 V, 3-ph 1.5 2.0 65 kA 15 A CC
480 V, 3-ph 2.2 3.0 65 kA 15 A CC
480 V, 3-ph 3.0 4.0 65 kA 25 A CC, J, T
480 V, 3-ph 4.0 5.0 65 kA 25 A CC, J, T
480 V, 3-ph 5.5 7.5 65 kA 25 A CC, J, T
480 V, 3-ph 7.5 10.0 65 kA 40 A J, T
480 V, 3-ph 11.0 15.0 65 kA 40 A J, T
480 V, 3-ph 15.0 20.0 100 kA 70 A J, T
480 V, 3-ph 18.5 25.0 100 kA 70 A J, T
480 V, 3-ph 22 30 100 kA 70 A J, T
480 V, 3-ph * 30 40 22 kA 125 A J, T
480 V, 3-ph * 37 50 22 kA 125 A J, T
480 V, 3-ph * 45 60 22 kA 125 A J, T
480 V, 3-ph * 55 75 22 kA 200 A J, T
480 V, 3-ph * 75 100 22 kA 200 A J, T
480 V, 3-ph * 90 125 22 kA 300 A J, T
480 V, 3-ph * 110 150 22 kA 300 A J, T
* Mains choke required
Electrical installaon
Connecon according to UL
151