Single−axis controllers
Wiring
Safety instructions for the installation according to UL/CSA
3
102
EDS94SPP101 EN 10.2
Device size 81 ... 91
E94BSxE1454 (145 A, 75 kW) ... E94BSxE2024 (202 A, 105 kW),
E94BSxE3664 (366 A, 190 kW) ... E94BSxE4604 (460 A, 240 kW):
Warnings!
ƒ Branch circuit protection:
– Suitable for use on a circuit capable of delivering not more than
100000 rms symmetrical amperes, 500 V max.
– Use specified fuses as shown in the table. Voltage of the fuses must at
least be suitable with the input voltage of the drive.
ƒ The integral solid state protection does not provide branch circuit protection
and that branch circuit protection has to be provided externally in
accordance with manufacturers instructions, the National Electrical Code
and any additional codes.
ƒ For information on the protection level of the internal overload protection
for a motor load in percent of FLA, see the corresponding Application
Manuals or Software Helps.
ƒ For information on rating and proper connection of the thermal protector
(only for connection to motors having integral thermal protection), see the
corresponding Application Manuals or Software Helps.
ƒ Maximum surrounding air temperature: 40 °C.
ƒ Use 75 °C copper wire only, except for control circuits.
ƒ These products are intended for use in a pollution degree 2 environment.
Branch circuit protection
Any class J fuse rated 600 Vac, limited to high−interrupting capacity 100 kA min.
Current limiting types below:
Type Fuse rating
E94BSxE1454 175 A
E94BSxE1724 200 A
E94BSxE2024 250 A
E94BSxE2454
(in preparation)
E94BSxE2924
E94BSxE3664
Supply input wire protection − The drive shall be protected by any UL Listed fuse in
accordance with the NEC.
(Note: The discrete internal semiconductor fuses are considered branch circuit protection)
E94BSxE4604
E94BSxE2454 (245 A, 130 kW) ... E94BSxE2924 (292 A, 150 kW):
(in preparation)