Regenerative power supply modules
Wiring
Important notes
6
315
EDS94SPP101 EN 10.2
6.6 Wiring
6.6.1 Important notes
ƒ Installation must
always be in accordance with the operating conditions specified in the Technical
data ( 286).
be carried out to EN 60204−1.
ƒ Please observe the following when selecting the cable type:
The cables used must comply with the approvals required for the application (e. g.
VDE, UL etc.).
Fuses and cable cross−sections must be dimensioned in accordance with the
specifications in the documentation for the basic device.
ƒ The described EMC properties are provided if the following conditions are complied
with:
The devices are mounted according to the arrangement concept described.
The prepared cables are used and remain unchanged.
Danger!
Hazardous electrical voltage
All power connections carry a hazardous electrical voltage for a longer time
after mains disconnection. Observe the information regarding the discharge
time on the device.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Before working on the power connections, wait at least until the discharge
time has passed (depending on the device, this may be up to 30 minutes).
ƒ Make sure that all power terminals are deenergised.