Power supply modules
Rated data
Operation at rated mains voltage 400 V
5
245
EDS94SPP101 EN 10.2
5.3.3 Operation at rated mains voltage 400 V
Input data
Mains Voltage Voltage range Frequency range
U
Lrated
[V] U
Lrated
[V] f [Hz]
3/PE AC 400 320 − 0 % ... 440 + 0 % 45 − 0 % ... 65 + 0 %
Voltage Continuous input power
Type [V] S
L
[kVA]
E94APNE0104 400 5.5
E94APNE0364 400 20.1
E94APNE1004 400 56.7
E94APNE2454 400 138
Output data
Mains Volta
g
e Volta
g
e ran
g
e Fre
q
uenc
y
ran
g
e
Voltage
U
DC
[V]
Voltage
range
U
DC
[V]
Frequency
range
f [Hz]
2/PE DC 565 455 − 0 % ... 620 + 0 %
Output current and output power
100 % 5−s cycle 3−min cycle
Type I
DC
[A] P
DC
[kW] I
DC
[A] P
DC
[kW] I
DC
[A] P
DC
[kW]
E94APNE0104 10 3.6 40 14.4 15 5.4
E94APNE0104
+ E94AZMP0084
10 4.9 40 19.6 15 7.4
E94APNE0364 36 13.0 108 39.0 54 19.5
E94APNE0364
+ E94AZMP0294
36 17.5 108 52.5 54 26.3
E94APNE1004 100 36.2 200 72.4 150 54.3
E94APNE1004
+ E94AZMP0824
100 48.6 200 97.2 150 72.9
E94APNE2454 245 88.6 368 133 368 133
E94APNE2454
+ E94AZMP2004
245 119 368 179 368 179
100 % Permanent rated values
5−s cycle Cycle for the second−range
(0.5 s overload/4.5 s recovery time with 75 % of the permanent rated value)
3−min cycle Cycle for the minute−range
(60 s overload/120 s recovery time with 75 % of the permanent rated value)